- The mass flows have to be corrected
- This causes an increase of the air flow rate of at least one fan
- The supply air quality is impaired by the exhaust air (see VDI 6022)
- The technical data can change
The carryover can be calculated in a simplified manner as follows:
Carryover M = f.n.T / 30 [m3/s] [01]
with rotor Depth T
speed of Rotation n
and half of rotor area f = d2.π / 8
Relative carryover Mr = M/V = 10.n.T / 3.v [%] [02]
with Speed v = V/f
und volumentric current V
Carryover occurs on both sides
It is important that the carryover occurs twice in the rotor:
- Once from the extract air to the supply air
- Once from the outside air to the exhaust air
The volumentric current balance is therefore correct at first glance: The missing outside air is replaced by the corresponding extract air. But it is exactly this that must be avoided, or at least compensated for by higher air flow rates.
Caution: The calculation above is idealised for visualisation purposes: The filling of the rotor - the rotor structure created from micro channels
through winding - is ignored!
(The rotor filling is usually defined by fill level FG = fF / f, whereby fF is the area covered by filling. This reduces the free section and the carryover while
the flow speed is increased by about 5 - 10%.)